DriveCore DC-15 AC Drive

15 kW variable-frequency drive · IP20 panel mount

Category
Motor control
Model
DC-15

The DC-15 is a 15 kW variable-frequency drive for three-phase motors. This manual covers the fan and capacitor service, the module-level repairs and the spare parts, for trained service staff working to the safety warnings below.

Danger
Lethal voltage: wait to dischargeThe DC link holds a lethal charge after power-off. Isolate, lock off, wait ten minutes and confirm below 50 V at the DC terminals before touching any component. Service by trained personnel only.
Tools & materials
ToolSpecNotes
Insulated screwdriver set1000 V VDETorx and slotted
DC-link voltmeter0–1000 V DCConfirm discharge < 50 V
Torque wrench2–20 N·mTerminal and busbar torque
ESD wrist strap1 MΩControl-board handling
Thermal pasteNon-siliconeIGBT module reseat
Fan & capacitor service
  1. Isolate the supply, lock off and wait ten minutes for the DC link to discharge.
  2. Confirm the DC-link voltage is below 50 V at the +/− terminals before touching anything.
  3. Record the parameter set, then remove the control board on its ESD strap.
  4. Replace the cooling fan or capacitor bank as required, observing polarity and torque.
  5. Reseat the control board, reload the parameters and re-torque all power terminals.
  6. Run the drive uncoupled and confirm no fault codes before returning to service.
Replacement parts
PartOrder codeQty
Cooling fanDC-15-FAN1
DC-link capacitor setDC-15-CAP1
Control boardDC-15-CTL1
Gate-driver boardDC-15-GDR1
Terminal cover kitDC-15-COV1
Return-to-service checks
  • Fault log downloaded before any reset
  • DC-link confirmed discharged below 50 V
  • Power terminals re-torqued to spec
  • Parameter set reloaded and verified
  • No fault codes on an uncoupled run